preloader

S8VK-S Switch mode

CÔNG TY TNHH KỸ THUẬT NTN
Brands
Mô tả sản phẩm

A Perfect Fit for Small Control Panels Coated PCBs for Better Resistance to Environment Connections for Easy Wiring

Control Panels: The Heart of Manufacturing Sites.
Evolution in control panels results in large evolution in production facilities.
And if control panel design, control panel manufacturing processes, and human interaction with them are innovated, control panel manufacturing becomes simpler and takes a leap forward.
OMRON will continue to achieve a control panel evolution and process innovation through many undertakings starting with the shared Value Design for Panel *1 concept for the specifications of products used in control panels.

*1 Value Design for Panel

S8VK-S Features 4

Our shared Value Design for Panel (herein after referred to as “Value Design”) concept for the specifications of products used in control panels will create new value to our customer’s control panels.
Combining multiple products that share the Value Design concept will further increase the value provided to control panels.

 

Specification

Power rating 30 W 60 W 120 W
Output voltage 24 V 24 V 24 V
Efficiency 115 VAC input *1 87% typ. 87% typ. 90% typ.
230 VAC input *1 86% typ. 89% typ. 92% typ.
Input Voltage range *2 Single-phase, 85 to 264 VAC, 90 to 350 VDC *12,
265 to 300 VAC (1 second)
Frequency *2 50/60 Hz (47 to 450 Hz) 50/60 Hz (47 to 63
Hz)
Input current 115 VAC input *1 0.58A typ. 1.1 A typ. 1.2 A typ.
230 VAC input *1 0.36A typ. 0.66 A typ. 0.63 A typ.
Power factor 0.9 min.
Leakage
current *3
115 VAC input 0.5 mA max.
230 VAC input 1 mA max.
Inrush current
*4 (for a cold
start at 25°C)
115 VAC input 16 A typ.
230 VAC input 32 A typ.
Output Rated output current 1.3 A 2.5 A 5 A
Rated output electric power 31.2 W 60 W 120 W
Maximum boost current 1.56 A 3 A 6 A
Voltage adjustment range *5 21.6 to 28 V (with V.DJ)
Ripple & Noise
voltage *6
100 to 240 VAC
input *1
190 mVp-p max. at
20 MHz of bandwidth
190 mVp-p max. at
20 MHz of bandwidth
110 mVp-p max. at
20 MHz of bandwidth
Input variation influence *7 0.5% max.
Load variation influence *8 1.5% max.
Temperature
variation
influence
115 to 230 VAC
input
0.05%/°C max.
Start up time
*4
115 VAC input *1 1000 ms max. 1000 ms max. 1000 ms max.
230 VAC input *1 1000 ms max. 1000 ms max. 1000 ms max.
Hold time *6 115 VAC input *1 30 ms typ. 20 ms typ. 45 ms typ.
230 VAC input *1 140 ms typ. 95 ms typ. 45 ms typ.
Additional
functions
Overload protection Yes, automatic reset
Overvoltage protection *9 Yes, 130% or higher of rated output voltage, power shut off (shut
off the input voltage and turn on the input again)
Series operation Yes (For up to two Power Supplies, external diodes are required.)
Parallel operation Yes (For up to two Power Supplies), Refer to Parallel Operation on
catalog for details.
Output indicator Yes (LED: Green)
Low-voltage detection output No
Insulation Withstand voltage 3.0 kVAC for 1 min. (between all input terminals and output
terminals), current cutoff 10 mA
2.0 kVAC for 1 min. (between all input terminals and PE terminals),
current cutoff 10 mA
1.0 kVAC for 1 min. (between all output terminals and PE
terminals), current cutoff 20 mA
Insulation resistance 100 MΩ min. (between all output terminals and all input
terminals/PE terminals) at 500 VDC
Environ-
ment
Ambient operating temperature *10 -40 to 70°C (Derating is required according to the temperature.
Refer to Engineering Data) (with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 95% RH max. (Storage humidity: 95% RH max.)
Vibration resistance 10 to 55 Hz, maximum 5G, 0.42 mm half amplitude for 2 h each in
X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Reliability MTBF 135,000 hrs min. (Refer to Data Sheet Reference Value)
Life expectancy *11 10 years min.
Con-
struction
Weight 250 g max. 250 g max. 400 g max.
Cooling fan No
Degree of protection IP20 by EN/IEC 60529
Standards Harmonic current emissions Conforms to EN 61000-3-2
EMI Conducted
Emissions
Conforms to EN 61204-3 Class B, EN 55011 Class B
Radiated
Emissions
Conforms to EN 61204-3 Class B, EN 55011 Class B
EMS Conforms to EN 61204-3 high severity levels
Approved Standards UL Listing:
UL 508,ANSI/ISA 12.12.01 (For 30 W and 60 W only Class2 Output: Per UL 1310)
cUL:
CSA C22.2 No107.1,
CSA C22.2 No213 (For 30 W and 60 W only Class2 Output: Per CSA C22.2 No.223)
UL UR:
UL 60950-1 (Recognition) OVCII (≤ 3000 m) Pol2
cUR:
CSA C22.2 No. 60950-1 OVCII (≤ 3000 m) Pol2
EN:
EN 50178 OVCIII (≤ 2000 m) OVCII (2000 m≤ and≤3000) Pol2,
EN 60950-1 OVCII (≤ 3000 m) Pol2
Conformed Standards PELV (EN/IEC 60204-1) *12
EN/IEC 61558-2-16:2009+A1:2013 *12
Marine Standards *12 Lloyd’s register (Except 30 W)
DNV GL (Except 30 W)
SEMI Conforms to F47-0706 (200 to 240 VAC input)

 

 

Power rating 240 W 480 W
Output voltage 24 V 24 V
Efficiency 115 VAC input *1 91% typ. 91% typ.
230 VAC input *1 93% typ. 93% typ.
Input Voltage range *2 Single-phase, 85 to 264 VAC, 90 to 350 VDC *12, 265 to 300 VAC
(1 second)
Frequency *2 50/60 Hz (47 to 63 Hz)
Input current 115 VAC input *1 2.4 A typ. 4.6 A typ.
230 VAC input *1 1.3 A typ. 2.3 A typ.
Power factor 0.9 min. 0.9 min.
Leakage
current *3
115 VAC input 0.5 mA max.
230 VAC input 1 mA max.
Inrush current
*4 (for a cold
start at 25°C)
115 VAC input 16 A typ.
230 VAC input 32 A typ.
Output Rated output current 10 A 20 A
Rated output electric power 240 W 480 W
Maximum boost current 15 A 30 A
Voltage adjustment range *5 21.6 to 28 V (with V.ADJ)
Ripple & Noise
voltage *6
100 to 240 VAC
input *1
100 mVp-p max.
at 20 MHz of bandwidth
130 mVp-p max.
at 20 MHz of bandwidth
Input variation influence *7 0.5% max.
Load variation influence *8 1.5% max.
Temperature
variation
influence
115 to 230 VAC
input
0.05%/°C max.
Start up time
*4
115 VAC input *1 1000 ms max. 1000 ms max.
230 VAC input *1 1000 ms max. 1000 ms max.
Hold time *6 115 VAC input *1 35 ms typ. 30 ms typ.
230 VAC input *1 35 ms typ. 30 ms typ.
Additional
functions
Overload protection Yes, automatic reset
Overvoltage protection *9 Yes, 130% or higher of rated output voltage, power shut off (shut
off the input voltage and turn on the input again)
Series operation Yes (For up to two Power Supplies, external diodes are required.)
Parallel operation Yes (For up to two Power Supplies), Refer to Parallel Operation on
catalog for details.
Output indicator Yes (LED: Green)
Low-voltage detection output Yes (Photoswitch output: 30 VDC max., 50 mA max.)
Insulation Withstand voltage 3.0 kVAC for 1 min. (between all input terminals and output
terminals), current cutoff 20 mA
2.0 kVAC for 1 min. (between all input terminals and PE terminals),
current cutoff 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminals),
current cutoff 20 mA
500 VAC for 1 min (between all output terminals and all low-voltage
detection output terminals), current cutoff 10 mA
Insulation resistance 100 MΩ min. (between all output terminals/all low-voltage
detection output terminals and all input terminals/PE terminals) at
500 VDC
Environ-
ment
Ambient operating temperature *10 -40 to 70°C (Derating is required according to the temperature.
Refer to Engineering Data) (with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 95% RH max. (Storage humidity: 95% RH max.)
Vibration resistance 10 to 55 Hz, maximum 5G, 0.42 mm half amplitude for 2 h each in
X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Reliability MTBF 135,000 hrs min. (Refer to Data Sheet Reference Value)
Life expectancy *11 10 years min.
Con-
struction
Weight 700 g max. 1150 g max.
Cooling fan No
Degree of protection IP20 by EN/IEC 60529
Standards Harmonic current emissions Conforms to EN 61000-3-2
EMI Conducted
Emissions
Conforms to EN 61204-3 Class B, EN 55011 Class B
Radiated
Emissions
Conforms to EN 61204-3 Class B, EN 55011 Class B
EMS Conforms to EN 61204-3 high severity levels
Approved Standards UL Listing: UL 508,ANSI/ISA 12.12.01
cUL:
CSA C22.2 No107.1,
CSA C22.2 No213
UL UR:
UL 60950-1 (Recognition) OVCII (≤ 3000 m) Pol2
cUR:
CSA C22.2 No.60950-1 OVCII (≤ 3000 m) Pol2
EN:
EN 50178 OVCIII (≤ 2000 m) OVCII (2000 m≤ and≤3000) Pol2,
EN 60950-1 OVCII (≤ 3000 m) Pol2
Conformed Standards PELV (EN/IEC 60204-1) *12
EN/IEC 61558-2-16:2009+A1:2013 *12
Marine Standards *12 Lloyd’s register
DNV GL
SEMI Conforms to F47-0706 (200 to 240 VAC input)

Order Code

Model List

Note: For details on normal stock models, contact your nearest OMRON representative.

 

Power ratings Rated input voltage Rated output
voltage
Rated output
current
Maximum
boost current
Model number
30 W 100 to 240 VAC
allowable range:
85 to 264 VAC or
90 to 350 VDC)
24 V 1.3 A 1.56 A S8VK-S03024
60 W 24 V 2.5 A 3 A S8VK-S06024
120 W 24 V 5 A 6 A S8VK-S12024
240 W 24 V 10 A 15 A S8VK-S24024
480 W 24 V 20 A 30 A S8VK-S48024

 

Mounting Brackets

 

Name Model
Front-mounting bracket (for 30 W and 60 W models) S82Y-VS10F
Side-mounting bracket (for 30 W and 60 W models) S82Y-VS10S
Front-mounting bracket (for 240 W and 480 W models) S82Y-VK10F
Product Danh mục